MODUtherm® fully integrates multiple technologies to minimise energy consumption and deliver reliable, trouble-free performance. Their modular design and construction reduces overall unit dimensions making them ideal for plant rooms with limited space. The high quality range features state-of-the-art high efficiency EC plug fans and the latest airtight casing construction.
MODUtherm’s innovative design incorporates EC fans that operate in parallel and are mounted adjacent to each other on an internal wall. The design provides inherent fan redundancy and will continue to operate even if there is a fault with one fan. The fans can be controlled by MODBUS or 0-10V signal and run independently or integrated into most building management systems.
The units are constructed with 50mm thick insulated panels that are fitted with the revolutionary AHU CLIP ‘n’ LOCK fastening system. This airtight system includes a synthetic cord and aluminium capping that give the unit a strong, rigid structure and allows the panels to be removed easily for maintenance and cleaning. AHU CLIP ‘n’ LOCK also provides a high thermal performance which reduces condensation and minimises energy loss. The high quality modular casing construction achieves both the highest degree of air tightness, rating “L1”, and the highest resistance to condensation, rating “TB1”, as defined in BS EN 1886:2007.
They are also available in Vertical or Horizontal configurations.
Model Number | CoilRows/(Fins/m) |
Air FlowL/s |
Air On (DB/WB) ℃ |
Air Off (DB/WB) ℃ |
Total (Capacity) kW |
Sensible (Capacity) kW |
Water Flow L/s |
Water Temp(Ent./Leav.) ℃ |
Pressure Drop(Water) kPa |
Pressure Drop(Air) Pa |
---|---|---|---|---|---|---|---|---|---|---|
MODU0711MZ | 8 / 472 | 15818 | 26 / 19 | 10.6 / 10.5 | 447.30 | 298.30 | 17.70 | 6 / 12 | 40.00 | 253.00 |
Model Number | CoilRows/(Fins/m) |
Air FlowL/s |
Air On (DB) ℃ |
Air Off (DB) ℃ |
Total(Capacity) kW |
Water Flow L/s |
Water Temp(Ent./Leav.) ℃ |
Pressure Drop(Water) kPa |
Pressure Drop(Air) Pa |
---|---|---|---|---|---|---|---|---|---|
MODU0711MZ | 1 / 394 | 15818 | 12 | 30.6 | 359.30 | 5.90 | 80 / 65 | 19.00 | 18.00 |
Model Number | Air FlowL/s |
Static Pressure(External) Pa |
Number of Fans |
Power(Full) kW |
Full Load(Current) Amps |
Speed (Fan) rps |
Power (Absorbed) KW |
---|---|---|---|---|---|---|---|
MODU0711MZ | 15818 | 450 | 6 | 5.00 x 6 | 7.60 x 6 | 1478 | 3.04 x 6 |
Model Number | 63 Hz |
125 Hz |
250Hz |
500 Hz |
1KHz |
2K Hz |
4K Hz |
8K Hz |
---|---|---|---|---|---|---|---|---|
MODU0711MZ | 82 | 90 | 96 | 92 | 90 | 84 | 82 | 79 |
Model Number | ALength |
BWidth |
CHeight |
DFPL Length |
EBase Height |
HR/A Opening# |
IR/A Opening# |
Coil Quantity | Weightkg |
---|---|---|---|---|---|---|---|---|---|
MODU0711MZ | 2230 | 3555 | 2335 | 1925 | 100 | 2995 | 2075 | 2 | 2617 |
Magnehelic’s easy to read gauges measure filter resistance, air velocity and pressure drop in a range of applications with high accuracy. They feature a mirrored overlay as standard in order to eliminate any parallax error when taking measurements.
Lights wired to individual switches on the exterior of Air Handling Unit. These robust lights come with Polypropylene base mount, glass diffuser and are protected with an external wire frame.
Clear Polycarbonate double viewport is mounted to the AHU door allowing internal components to be viewed without the need to shut down unit during operation.
Sheet metal roof allows protection from the weather. Includes 90° ridges to help clear water
Please fill out the form below and we will contact you shortly