The unique design of the MINItherm® fan coil range offers the latest double skin construction in a compact air handling unit. The units are available in Horizontal or Vertical configurations making them ideal for ceilings or plant rooms where space is limited.
MINItherm units are purpose-built to enable easy access for servicing and are well suited to projects where performance and value are important. They include high efficiency EC plug fans that can be controlled by MODBUS or 0-10V signal. The fans can run independently or integrated into most building management systems.
The units are constructed with 50mm thick insulated panels that are fitted with the revolutionary AHU CLIP ‘n’ LOCK fastening system. This airtight system includes a synthetic cord and aluminium capping that gives the unit a strong, rigid structure and allows the panels to be removed easily for maintenance and cleaning. AHU CLIP ‘n’ LOCK also provides a high thermal performance which reduces condensation and minimises energy loss. The high quality modular casing construction achieves both the highest degree of air tightness, rating “L1”, and the highest resistance to condensation rating “TB1”, as defined in BS EN 1886:2007.
Model Number | CoilRows/(Fins/m) |
Air FlowL/s |
Air On (DB/WB) ℃ |
Air Off (DB/WB) ℃ |
Total (Capacity) kW |
Sensible (Capacity) kW |
Water Flow L/s |
Water Temp(Ent./Leav.) ℃ |
Pressure Drop(Water) kPa |
Pressure Drop(Air) Pa |
---|---|---|---|---|---|---|---|---|---|---|
HMEP-5900-FCO | 6 / 472 | 5902 | 26 / 19 | 11.1 / 11.0 | 159.5 | 107.3 | 6.3 | 6 / 12 | 29 | 190 |
Model Number | CoilRows/(Fins/m) |
Air FlowL/s |
Air On (DB) ℃ |
Air Off (DB) ℃ |
Total(Capacity) kW |
Water Flow L/s |
Water Temp(Ent./Leav.) ℃ |
Pressure Drop(Water) kPa |
Pressure Drop(Air) Pa |
---|---|---|---|---|---|---|---|---|---|
HMEP-5900-FCO | 1 / 394 | 5902 | 12 | 30.6 | 134.1 | 2.2 | 80 / 65 | 19 | 18 |
Model Number | Air FlowL/s |
Static Pressure(External) Pa |
Number of Fans |
Power(Full) kW |
Full Load(Current) Amps |
Speed (Fan) rps |
Power (Absorbed) KW |
---|---|---|---|---|---|---|---|
HMEP-5900-FCO | 5902 | 450 | 2 | 5.40 x 2 | 8.20 x 2 | 32 | 3.50 x 2 |
Model Number | 63 Hz |
125 Hz |
250Hz |
500 Hz |
1KHz |
2K Hz |
4K Hz |
8K Hz |
---|---|---|---|---|---|---|---|---|
HMEP-5900-FCO | 81 | 84 | 92 | 90 | 90 | 84 | 81 | 79 |
Model Number | ALength |
BWidth |
CHeight |
EBase Height |
FS/A Opening* |
GS/A Opening* |
HR/A Opening# |
IR/A Opening# |
Weightkg |
---|---|---|---|---|---|---|---|---|---|
HMEP-5900-FCO | 1925 | 2030 | 1725 | 100 | 1520 | 1485 | 1575 | 1880 | 648 |
Magnehelic’s easy to read gauges measure filter resistance, air velocity and pressure drop in a range of applications with high accuracy. They feature a mirrored overlay as standard in order to eliminate any parallax error when taking measurements.
Lights wired to individual switches on the exterior of Air Handling Unit. These robust lights come with Polypropylene base mount, glass diffuser and are protected with an external wire frame.
Clear Polycarbonate double viewport is mounted to the AHU door allowing internal components to be viewed without the need to shut down unit during operation.
Sheet metal roof allows protection from the weather. Includes 90° ridges to help clear water