Sunday, December 22, 2024

The SM Series TM of Fan Coil Units is ideal for in-ceiling installations and include fans driven by AC single phase motors. Their quality 1.2mm galvanised metal casing is internally lined with 20mm polyethylene insulation foam to provide resistance to condensation.

Each side of the unit includes a sealed access panel. These units are available in 5 standard sizes with air flows from 200 to 1900 litres per second and come in both horizontal and vertical configurations.


Downloads

Technical Data

Cooling

Model Number Coil
Rows/(Fins/m)
Air Flow
L/s
Air On
(DB/WB) ℃
Air Off
(DB/WB) ℃
Total
(Capacity) kW
Sensible
(Capacity) kW
Water Flow
L/s
Water Temp
(Ent./Leav.) ℃
Pressure Drop
(Water) kPa
Pressure Drop
(Air) Pa
SMA14-H 5 / 472 1400 26 / 19 12.2 / 11.91 33.90 23.60 1.30 6 / 12 23.00 158.00

Heating

Model Number Coil
Rows/(Fins/m)
Air Flow
L/s
Air On
(DB) ℃
Air Off
(DB) ℃
Total
(Capacity) kW
Water Flow
L/s
Water Temp
(Ent./Leav.) ℃
Pressure Drop
(Water) kPa
Pressure Drop
(Air) Pa
SMA14-H 1 / 394 1400 12 29.5 30.00 0.49 80 / 65 2.10 18.00

Motor Data

Model Number Air Flow
L/s
Static Pressure
(External) Pa
Number of
Fans
Power
(Full) kW
Full Load
(Current) Amps
Speed
(Fan) rps
Power
(Absorbed) KW
SMA14-H 1400 250 1 0.80 x 1 5.80 x 1 23 / 22 / 21 x 1

Sound Data

Model Number 63
Hz
125
Hz
250
Hz
500
Hz
1K
Hz
2K
Hz
4K
Hz
8K
Hz
SMA14-H 58 64 67 66 66 62 60 55
Dimensional Drawing
Dimensional Diagram
Model Number A
Length
B
Width
C
Height
D
FPL Length
E
Base Height
G
S/A Opening*
H
R/A Opening#
Weight
kg
SMA14-H 1750 1150 1750 948 262 1473 381 160
All dimensions in mm.
Weights are an approximation only.
* S/A Opening = Outlet # R/A Opening = Inlet.
Contact us about this product - "SMA14-H"

Please fill out the form below and we will contact you shortly

*

*