The SLIMtherm TM range of Fan Coil Units combines the benefits of a quality double skin casing construction and an extra low profile design. Units are also available in horizontal configurations.
SLIMtherm units in a vertical configuration are designed to minimize the plant room space needed for installation. The compact dimensions of the vertically configured SLIMtherm units makes them ideal for projects where plant room space is restricted.
The units are constructed with 25mm thick insulated panels that are fitted with the revolutionary FCU CLIP ‘n’ LOCK fastening system. This airtight system includes a synthetic cord and aluminium capping that gives the unit a strong, rigid structure and allows the panels to be removed easily for maintenance and cleaning. The high quality modular casing construction achieves the highest degree of air tightness, rating “L1”, as defined in BS EN 1886:2007.
SLIMtherm units include high efficiency EC plug fans that can be controlled by MODBUS or 0-10V signal and run independently or integrated into most building management systems. The EC fans can be easily accessed for maintenance or replacement by removing an FCU CLIP ‘n’ LOCK side panel.
Model Number | CoilRows/(Fins/m) |
Air FlowL/s |
Air On (DB/WB) ℃ |
Air Off (DB/WB) ℃ |
Total (Capacity) kW |
Sensible (Capacity) kW |
Water Flow L/s |
Water Temp(Ent./Leav.) ℃ |
Pressure Drop(Water) kPa |
Pressure Drop(Air) Pa |
---|---|---|---|---|---|---|---|---|---|---|
SLV-1600-FCO | 5 / 472 | 1610 | 26 / 19 | 12.12 / 11.81 | 39.50 | 27.30 | 1.20 | 6 / 12 | 33.00 | 158.00 |
Model Number | CoilRows/(Fins/m) |
Air FlowL/s |
Air On (DB) ℃ |
Air Off (DB) ℃ |
Total(Capacity) kW |
Water Flow L/s |
Water Temp(Ent./Leav.) ℃ |
Pressure Drop(Water) kPa |
Pressure Drop(Air) Pa |
---|---|---|---|---|---|---|---|---|---|
SLV-1600-FCO | 1 / 394 | 1610 | 12 | 30.6 | 36.60 | 0.60 | 80 / 65 | 22.00 | 18.00 |
Model Number | Air FlowL/s |
Static Pressure(External) Pa |
Number of Fans |
Power(Full) kW |
Full Load(Current) Amps |
Speed (Fan) rps |
Power (Absorbed) KW |
---|---|---|---|---|---|---|---|
SLV-1600-FCO | 1610 | 250 | 3 | 0.50 x 3 | 2.30 x 3 | 50 | 0.50 x 3 |
Model Number | 63 Hz |
125 Hz |
250Hz |
500 Hz |
1KHz |
2K Hz |
4K Hz |
8K Hz |
---|---|---|---|---|---|---|---|---|
SLV-1600-FCO | 71 | 78 | 78 | 79 | 80 | 80 | 75 | 70 |
Model Number | ALength |
BWidth |
CHeight |
DFPL Length |
FS/A Opening* |
GS/A Opening* |
HR/A Opening# |
IR/A Opening# |
Weightkg |
---|---|---|---|---|---|---|---|---|---|
SLV-1600-FCO | 950 | 1980 | 808 | 80 | 1470 | 220 | 297 | 1785 | 237 |