Tuesday, November 12, 2024

The SLIMtherm TM range of Fan Coil Units combines the benefits of a quality double skin casing construction and an extra low profile design. Units are also available in vertical configurations.

SLIMtherm units with a horizontal configuration are designed to be hung within a ceiling void. The extra low profile design makes the horizontally configured SLIMtherm units an ideal solution for low ceiling height applications.

The units are constructed with 25mm thick insulated panels that are fitted with the revolutionary FCU CLIP ‘n’ LOCK fastening system. This airtight system includes a synthetic cord and aluminium capping that gives the unit a strong, rigid structure and allows the panels to be removed easily for maintenance and cleaning. The high quality modular casing construction achieves the highest degree of air tightness, rating “L1”, as defined in BS EN 1886:2007.

SLIMtherm units include high efficiency EC plug fans that can be controlled by MODBUS or 0-10V signal and run independently or integrated into most building management systems. The EC fans can be easily accessed for maintenance or replacement by removing an FCU CLIP ‘n’ LOCK side panel.


Downloads

Technical Data

Cooling

Model Number Coil
Rows/(Fins/m)
Air Flow
L/s
Air On
(DB/WB) ℃
Air Off
(DB/WB) ℃
Total
(Capacity) kW
Sensible
(Capacity) kW
Water Flow
L/s
Water Temp
(Ent./Leav.) ℃
Pressure Drop
(Water) kPa
Pressure Drop
(Air) Pa
SLH-1600-FCO 5 / 472 1600 26 / 19 12 / 12 11.81 39.5 27.3 1.2 6 / 12 33 158

Heating

Model Number Coil
Rows/(Fins/m)
Air Flow
L/s
Air On
(DB) ℃
Air Off
(DB) ℃
Total
(Capacity) kW
Water Flow
L/s
Water Temp
(Ent./Leav.) ℃
Pressure Drop
(Water) kPa
Pressure Drop
(Air) Pa
SLH-1600-FCO 1 / 394 1600 12 30.6 36.6 0.6 80 / 65 22 18

Motor Data

Model Number Air Flow
L/s
Static Pressure
(External) Pa
Number of
Fans
Power
(Full) kW
Full Load
(Current) Amps
Speed
(Fan) rps
Power
(Absorbed) KW
SLH-1600-FCO 1600 250 3 0.50 x 3 2.30 x 3 50 0.50 x 3

Sound Data

Model Number 63
Hz
125
Hz
250
Hz
500
Hz
1K
Hz
2K
Hz
4K
Hz
8K
Hz
SLH-1600-FCO 71 78 78 79 80 80 75 70
Dimensional Drawing
Dimensional Diagram
Model Number A
Length
B
Width
C
Height
F
S/A Opening*
G
S/A Opening*
H
R/A Opening#
I
R/A Opening#
Weight
kg
SLH-1600-FCO 540 1980 808 1470 350 399 1785 175
All dimensions in mm.
Weights are an approximation only.